User Guide
Table Of Contents
PRODUCT DATA
95C-10711-01
V135 3-Way Mixing or Diverting
Valve
APPLICATION
The Honeywell Braukmann V135 valve is designed for
hydronic heating systems and can be applied as a mixing
valve or a diverting valve. The V135 is normally used with the
T100R series thermostatic control, which is equipped with a
strap-on pipe sensor for attaching to the heating system pipe
by means of a clamp. A plastic handle is also provided with
the V135 for manual operation of the valve.
SPECIFICATIONS
Construction
Body of bronze, internal parts of high-quality engineering plas-
tic, stainless steel stem and high-quality elastomer materi-
als.
Maximum Temperature Rating: 248 °F (120 °C)
Maximum System Pressure: 232 psi.
Maximum Differential Pressure: 147 psi.
Stroke Length: 0.08 in. (2 mm)
Cv rating and valve size: See Table 1.
Table 1. Flow Capacities.
a
Cv= U.S. GPM at 1psi differential pressure.
Fig. 1. V135A flow chart.
Dimensions: See Fig. 2 and Table 2.
Size (in.) Cv Factor
a
3/4 3.7
15.8
1-1/4 5.8
1-1/2 11.7
M28700
PRESSURE DROP (PSI)
FLOW RATE (USGPM)
3/4 IN.
1 &
1-1/4 IN.
1-1/2
& 2 IN.
0.1
1.0
4.0
10
30
70
1.0 3.0 10 30