Product Overview
V135 DIVERTING AND MIXING VALVE
Honeywell y Subject to change 3 EN0H-2800GE25 R0110
Accessories
NOTE: For detailed information see T100R/RS data sheet.
Please Note:
• To avoid stone deposit and corrosion the composition of the
medium should conform with VDI-Guideline 2035
• Additives have to be suitable for EPDM sealings
• System has to be flushed thoroughly before initial operation
with all valves fully open
• Any complaints or costs resulting from non-compliance with
above rules will not be accepted by Honeywell
• Please contact us if you should have any special require-
ments or needs
Valve insert
V135A-1/2VE
V135A-1VE
V135A-11/2VE
Thermostat with remote sensor (screw-in sensor)
With R1/2" immersion pocket
Setting range 10...50°C (50...122°F)
T100R-AA
With R1/2" immersion pocket
Setting range 30...70°C (86...158°F)
T100R-AB
With R1/2" screw in sensor
Setting range 10...50°C (50...122°F)
T100RS-DA
With R1/2" screw in sensor
Setting range 30...70°C (86...158°F)
T100RS-DB
Smart-T thermal actuator (on/off control only)
MT4...
NOTE: Please refer to MT4 data sheet for exact model
number
Installation Examples
Flow Diagram A - AB and B - AB
Mixing valve on primary side Mixing valve on secondary side Diverting valve on primary side
hot water
cold wate
r
B
AB
A
hot water
cold wate
r
hot water
cold wate
r
Flow coefficient kv in m
3
/h
Stroke in mm
DN25 + DN32
DN25 + DN32
DN15
DN20
DN15
DN20