9 68-0262—09
Fig. 11. Remove lamp or bulb.
4. Holding the lamp handle, wipe the lamp glass using
a soft cloth dampened with window cleaner. If you
touch the lamp glass with your hands, be sure to
clean the area of any oils left from bare hands. See
Fig. 12.
Fig. 12. Clean glass with soft cloth.
5. Also wipe away any dust that may have collected
between the lamp light indicator on the base and the
black lamp base. See Fig. 13.
Fig. 13. Wipe lamp light indicator base.
6. Dry bulbs with a clean, dry cloth.
7. Insert the lamp handle into the base with the lamp
light indicator at the eleven o’clock position. Con-
tinue pushing and gently rotating counterclockwise
until the lamp handle inserts fully into the base. See
Fig. 14.
Fig. 14. Position lamp handle for insertion back into
lamp base.
8. Rotate the lamp handle clockwise until it snaps into
place with the lamp light indicator aligned with the
raised button on the unit cover. See Fig. 15.
Fig. 15. Snap lamp handle into place.
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
Never look at bulbs while illuminated.
View illumination only through lamp light indicator
located on lamp handle.
To prevent exposure to ultraviolet light, disconnect
power to ultraviolet system before servicing any
part of heating and air conditioning system.
M22841
M22843
LAMP LIGHT
INDICATOR BASE
M22845
M22847
M22849