Install Instructions

UV100E ULTRAVIOLET SYSTEMS
68-0262—09 6
CAUTION
Breakable Glass Hazard.
Can cause personal injury.
Be careful when inserting bulb(s) into lamp base.
Wear protective gloves when handling bulb(s).
MERCURY NOTICE
This device contains mercury in the sealed
ultraviolet bulb(s). Do not place your used bulb(s)
in the trash. Dispose of properly.
Broken Bulb Cleanup.
Do not use a household vacuum.
Sweep debris into a plastic bag and dispose of
properly.
Contact your local waste management authority
for instructions regarding recycling and the proper
disposal of old bulb(s).
11. Insert the lamp handle into the base unit with the
lamp light indicator at the eleven o’clock position
(left of the raised button on the unit cover). See
Fig. 4. If you touch the lamp glass with your hands,
use a cloth to wipe fingerprints from the glass. See
Fig. 5.
Fig. 4. Insert lamp handle into base unit.
Fig. 5. Use cloth to wipe fingerprints from glass.
12. Continue lightly pushing in on the lamp handle
while rotating it slowly counterclockwise. This
should cause the lamp handle to drop into the
bottom of the lamp well.
13. Rotate the lamp handle clockwise until it snaps into
place with the lamp light indicator aligned with the
raised button on the unit cover. See Fig. 6.
Fig. 6. Snap lamp handle into place.
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
View illumination only through lamp light indicator
located on lamp handle.
To prevent exposure to ultraviolet light, disconnect
power to ultraviolet system before servicing any
part of heating and air conditioning system.
NOTE: If you desire to communicate with other appli-
ances using your Enviracom communication bus,
go on to step 14; if not, go directly to step 15.
14. Hook up corresponding appliance wires to the
Enviracom communication bus located on the bot-
tom of the UV device base. Be sure to loop wire of
other Enviracom appliances or Enviracom common
node around the UV base Enviracom screw termi-
nals 1, 2 and 3. See Fig. 7.
Fig. 7. Looping Enviracom appliance or common node
wire around UV Enviracom base screw terminals.
15. Plug the cord into the nearby 120 Vac electrical
outlet.
M22847
M22843
1
RESET
2 3
M20242