SPECIFICATIONS
Thermostat Description: See Table 1.
Electrical Ratings: See Table 2.
Temperature:
Ratings:
Operating Ambient:
TB7100: 0°F to 120°F (-18°C to 49°C).
C7189U: 5% to 95%.
Shipping: -30 °F to 150 °F (-34.4°C to 65.6°C).
Display Accuracy: ±1°F (±0.5°C).
Setpoint:
Range:
Heating: 40°F to 90°F (4°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Default Settings: See Table 3.
Humidity Ratings (RH, non-condensing):
TB7100: 5% to 90%.
C7189U: 5% to 95%.
Table 1. Thermostat Description.
Table 2. Electrical Ratings
Table 3. Energy-saving Default Program Settings.
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour.
Cooling: Selectable 1 - 6 cycles per hour.
Interstage Differential:
Droopless control. Once the first stage is running at 90%
load, the thermostat energizes the second stage.
Cool Indication: Displays “Cool On” when Cool is acti-
vated.
Heat Indication: Displays “Heat On” when Heat is acti-
vated.
Auxiliary Heat Indication: Displays “Aux. Heat On” when
Auxiliary Heat is activated.
Clock Accuracy: ±1 minute per month.
Finish:
TB7100: Premier White® color.
C7189U Wall Mount Remote Indoor Sensor: Premier
White® color.
TR21 Wall Mount Remote Indoor Sensor: Premier White®
color.
Batteries:
Two replaceable AA alkaline batteries: Power thermostat
when 24 Vac common is not used.
Non-replaceable lithium battery with ten-year life: Under
normal conditions holds calendar and time settings.
NOTE: Alkaline batteries keep calendar and time if lith-
ium battery is no longer functional.
Resistance Characteristics of Remote Sensors:
C7189U Remote Indoor Sensor: 10K ohm NTC.
C7772 Flush-Mount Remote Indoor Sensor: 20K ohm
NTC.
TR21 Wall-Mount Remote Indoor Sensor: 20K ohm NTC.
TR21-A Wall-Mount Remote Indoor Sensor: 10K ohm NTC.
Calibration (TB7100, C7089U, C7189U, T7770A):
No field calibration required.
Mounting Means:
TB7100: Direct wall-mount using mounting screws and
anchors provided. Fits standard vertical or horizontal
2 in. x 4 in. junction box.
C7189U, TR21: Mounts directly on the wall using mount-
ing screws and anchors provided. Fits a vertical 2 x 4 in.
junction box.
Cover Plate:
32003796-001 Cover Plate is used to cover marks left on
the wall by the old thermostat.
Feature Description
Powering
methods
Battery only
24 Vac only
24 Vac with battery backup
System types Conventional (1 Heat, 1 Cool Stages)
Heat Pump (up to 2 Heat,
1 Cool
Stages)
2 Pipe Fan Coil
2 Pipe Fan Coil with Auxiliary Heat
4 Pipe Fan Coil
PTAC (up to 2 Heat, 1 Cool)
Changeover Manual or Auto changeover selectable
System
setting
Heat-Off-Cool-Auto
Fan setting Auto-On
Fan Speeds Low, Medium, High
Remote
Setback
Remote Setback Input for occupancy
sensor or DDC Setback
Fan Ramping
Algorithm
VersaSpeed™ Fan Ramping Algorithm for
Automatic Fan Speed Selection (fan coil
and PTAC applications)
Terminal
Voltage
(50/60 Hz)
Running
Current
W (Heating) 20 - 30 Vac 0.02 - 1.0 A
Y (Cooling) 20 - 30 Vac 0.02 - 1.0 A
G (Fan), G
2
, G
3
20 - 30 Vac 0.02 - 0.60 A
Schedule
Period Time
Setpoints
Heat Cool
Occ1 8:00 am 70 °F (21 °C) 75 °F (24 °C)
Unocc1 10:00 pm 55 °F (10 °C) 85 °F (29.5 °C)
Occ2
Unocc2