Product Overview

TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
63-2675—04 14
0535 Temporary Occupied
Duration Limit
3 0–12 hours 0 means no limit.
0540 Number of Periods 4 2—2 Periods
4—4 Periods
Does not appear if Non-programmable is chosen (ISU 0160).
Applies to all days of the week. If 2 is selected the Cancel Period
option will not appear on the display.
0580 Minimum Compressor
Off Time
50Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
Only shown if system has cool stages in CNV, Heat Pump, PTAC
(ISU 0170).
0600 Heat Temperature
Range Stops
90 40 to 90°F (4 to 32°C) Only shown if system has heat stages (ISU 0170).
0610 Cool Temperature
Range Stops
50 50 to 99°F (10 to 37°C) Only shown if system has cool stages (ISU 0170).
0640 Clock Format 12 12—12 Hour
24—24 Hour
0650 Extended Fan-on time
Heat
00Off
90—90 seconds
Not displayed if fan set to fossil or cool only systems (ISU 0170)
0660 Extended Fan-on time
Cool
00Off
40—40 seconds
Only shown if system has cool stages. (ISU 0170)
0670 Keypad Lockout 0 0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Partial Lockout 3
4—Fully Locked
Unlocked: All functions accessible.
Partial 1: Locks out schedule and system changes.
Partial 2: Locks out schedule, system, and fan changes.
Partial 3: Locks out schedule, system, fan, and up/down arrow
changes.
Full: Entire interface locked/non-functional.
0680 Temperature Control
Heat
2 1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has heat stages (ISU 0170).
Only integral gains are affected by this setting. The setting affects
control operation in all control regimes (not just recovery or
setpoint change).
0685 Recovery Heat Ramp
Rate
5 0-20°F/hour Only shown if system has heat stages (ISU 0170).
0 disables the ramped recovery (step setpoint change at period
start time).
0690 Temperature Control
Cool
2 1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has cool stages (ISU 0170).
Only integral gains are affected by this setting. The setting affects
control operation in all control regimes (not just recovery or
setpoint change).
0695 Recovery Cool Ramp
Rate
3 0-20°F/hour Only shown if system has cool stages (ISU 0170).
0 disables the ramped recovery (step setpoint change at the
period start time).
0700 Temperature Display
Offset
0 -3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
This offset applies to both the control temperature and to the
display temperature for indoor sensor (and remote indoor sensor).
0710 Restore Factory Defaults 0 0—No
1—Yes
Resets all ISU parameters to default values and resets the
schedule to default. Retains only calendar settings and time.
0720 Screen Display 2 0—Display Room Temperature
1—Display Setpoint
2—Display Both
Table 6. Installer Setup Menu. (Continued)
Installer
Setup
Number Installer Setup Name
Default
Setting All Settings Notes