Product Overview

TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
13 63-2675—04
0310 Deadband 3°F (2°C) 2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
Only shown if Automatic Changeover selected (ISU 0300).
0320 Temperature Indication
Scale
00°F
1—°C
0330 Daylight Saving 1 0—Disabled
1—Enabled (US)
0340 Remote Temp
Sensor/Remote
Setback/Changeover
Input
00None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe Fan Coil modes
only
4—Changeover 2 pipe Fan Coil modes
only
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
0340
(Non-
programm
able)
Remote Temp
Sensor/Remote
Setback/Changeover
Input
00None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe Fan Coil modes
only
4—Changeover 2 pipe Fan Coil modes
only
5—Remote Setback
6—Remote Setback
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Hotel card NO, with 1 second software delay going from UnOcc to
Occupied; 2 minute delay going from Occupied to UnOcc.
Hotel Card NC, with 1 second software delay going from UnOcc to
Occupied; 2 minute delay going from Occupied to UnOcc.
0341 Delay for Remote
Setback
00No Delay
2—2 Minute Delay
Only shown if Remote Setback (ISU 0340) is enabled.
0342 Override Option (only
available in non-
programmable mode)
0 0—No Override
1—Override
This option is only available for non-programmable mode (ISU
0160)
0343 Unoccupied Heating
Setpoint (only when
remote setback enabled)
60°F 50-65°F
10-18°C
0346 Unoccupied Cooling
Setpoint (only when
remote setback is
enabled)
80°F 75-90°F
24-30°C
0347 Fan Ramping 1 0—Disabled (Lo, Med, Hi)
1—Enabled
To enable the fan ramping algorithm. Only available for fan coil or
PTAC applications (ISU 0170)
0348 Fan Mode 0 0—User can choose Cycle or Constant 3
speed: Low->Med->
High->Auto-> Low 1—
Cycle Only - Auto only
To select a particular fan mode: Auto is the fan ramp mode. If
ramping is not selected, fan mode automatically defaults to Low
Med High (Constant only) and ISU 0348 is unavailable. Only
available for fan coil or PTAC applications (ISU 0170)
0349 Auto Fan Reset 0 0—Inactive 1—Reset
back to Auto after 2 hours
2—Reset back to Auto after 4 hours
The timer will be set after the user selects the constant fan speed.
Fan will be set to Auto automatically when time out. The start time
is calculated after initial call for heat/cool is satisfied, then 2 hour
timing begins.
The timer will be set after the user selects the constant fan speed.
Fan will be set to Auto automatically when time out. The start time
is calculated after initial call for heat/cool is satisfied, then 4 hour
timing begins. Only available for fan coil or PTAC applications (ISU
0170)
Table 6. Installer Setup Menu. (Continued)
Installer
Setup
Number Installer Setup Name
Default
Setting All Settings Notes