TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
63-2675—04 12
INSTALLER SETUP NUMBERS (ISU), SETTINGS, AND TESTS (TABLE 6)
Use the Installer System Test to test the heating, cooling
and fan. Refer to the latter portion of Table 6.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling
and fan. The setting chosen for System Type (ISU
0170) can prevent some System Test Numbers
from appearing.
NOTE: Unless otherwise noted, setup items are accessi-
ble through only the Installer setup and not the
User setup.
Table 6. Installer Setup Menu.
Installer
Setup
Number Installer Setup Name
Default
Setting All Settings Notes
0120 Date (Year Upper) 20 20—21 Available year range: 2001 - 2178
0130 Date (Year Lower) 08 00-99 Available year range: 2001 - 2178
0140 Date (Month) 6 1-12
0150 Date (Day) 15 1-31 (Month Dependent)
0160 Schedule Options 4 0—Non-Programmable
4—Programmable
0170 System Selection 1 1—1H/1C Conv
2—1H w/o fan
3—1H with fan
4—1C
5—1H/1C HP
6—2H/1C HP
7—4 pipe Fan Coil
8—2 pipe Fan Coil
9—2 pipe Fan Coil w/ Aux Heat
10—PTAC 1H/1C (Hi speed, Lo speed
Fan)
11—PTAC 2H/1C (Hi speed, Lo speed
Fan)
Relay Y is used for 2 pipe fan coil output relay.
0180 Heat Fan Operation 0 0—Fossil
1—Electric
Only shows up if conventional system with heat stages and fan
capability is selected (ISU 0170). If heat pump is selected, fan
defaults to electric. If fan coil or PTAC modes are selected, fan
defaults to electric (does not show up).
0185 Pre-occupancy Purge
Duration
0 0—no duration
1—one hour
2—two hours
3—three hours
Shown only if system has fan and schedule is programmable (ISU
0160).
Pre-occupancy purge is enabled by a nonzero duration.
0190 Reversing Valve
O/B
0 0—O (O/B On Cool)
1—B (O/B On Heat)
Only shown if heat pump or PTAC system is selected.
0220 Cycles Per Hour (CPH)
for first stage
cooling/compressor
3 1-6 Only shown if system has cool stages (ISU 0170). Shown for heat
pump, fan coil, PTAC, and conventional cooling stages.
0240 CPH for first stage heat 5 1-12 Only shown if system is conventional with heat stages, 4 pipe fan
coil, 2 pipe fan coil (ISU 0170).
0270 CPH for Em Heat 9 1-12 Only shown if HP with reheat, 2 pipe fan coil with reheat, and PTAC
with reheat (ISU 0170).
0280 Continuous Backlight 0 0—No
1—Yes
Always shown; however, if AC power is not present, the option is
overridden and normal backlight operation occurs.
0300 Changeover 1 0—Manual
1—Auto
Only shown if system has both heat and cool stages (ISU 0170).
Shown for CNV, HP, PTAC and 4 pipe fan coil (ISU 0170). Not
shown for 2 pipe fan coil modes.