Install Instructions
Table Of Contents
® U.S. Registered Trademark
Copyright © 2001 Honeywell • •All Rights Reserved
INSTALLATION INSTRUCTIONS
69- 1526
Static Pressure Control (SPC)
APPLICATION
The Static Pressure Control (SPC) is an adjustable,
single-pole double-throw differential pressure switch. It is
used to control a floating-type modulating damper for
bypass zone applications. Acceptable dampers are
MARD and CDO-51 or the 90-second ML6161 Actuator.
The contacts are rated at 125 VA. See Fig. 1.
INSTALLATION
Selecting the SPC Mounting Location
1.
Locate the SPC near the supply air ductwork. Fig.
1 shows the dimensions in in. (mm).
2.
Orient it with the adjustment screw on the top as
shown in Fig. 2.
3.
Use the supplied bracket and hardware.
Fig. 1. SPC dimensions in in. (mm).
Fig. 2. Correct mounting orientation.
Mounting the SPC
1.
Mount the SPC near the supply ductwork in the
upright position.
2.
Install one threaded barb fitting into the lower pres-
sure port as shown in Fig. 3.
3.
Attach the supplied tubing to the barbed fitting.
4.
Drill a 1/2 in. hole into the ductwork and insert the
supplied surface mount duct fitting.
5.
Seal it with a small amount of silicone sealant and
attach with the two supplied self-tapping screws.
6.
Connect the opposite end of the tubing to the
barbed end of the duct fitting.
4-1/16 (103)
5
(127)
M19018
GREY SPRING
ON-OFF
INDICATOR
SWITCH
RANGE SCALE
ADJUSTMENT/INDICTOR
M19019
GREY SPRING