Install Instructions
PS1202C, PS2402C REPLACEMENT POWER SUPPLY KITS FOR ELECTRONIC AIR CLEANERS
69-1137EF—01 4
Fig. 6. Removing F90A Power Supply Assembly.
Install New Power Supply
 When replacing the power supply, refer to the 
appropriate wiring diagram. See Fig. 7 through Fig. 20.
 Install new W8600E terminal block and wiring using 
screws removed previously.
 When replacing the power supply, reuse the lead wires 
remaining in the air cleaner when removing the old 
power supply board and performance indicator board.
 Note that the F52 uses a mounting plate that has a 
rubber bumper; turn over the power supply and pry the 
rubber bumper off the bottom.
 Align the mounting holes and mount the new power 
supply in the air cleaner using the sheet-metal screws 
removed earlier. Orient the terminal strip (on selected 
models) so that pin 1 is at the top.
IMPORTANT
Do not splice ionizer and collector leads. These 
leads must be unbroken to avoid electrical shock 
through the connector or tape covering the 
splice.
 Route the remaining leads so the red ionizer and black 
collector leads are separate from the power supply and 
light leads. Route all leads around, rather than over, 
the power supply board. Keep all leads away from high 
voltage leads. On single-cell, duct mounted cleaners, 
route the performance indicator output lead (4-wire 
thermostat cable) to the rear of the power supply 
assembly.
 Connect the leads to the quick-connect terminals on 
the new power supply. See Fig. 7 through Fig. 20.
 Route the leads through the cable clamp and hook the 
cable clamp to the tab on the left front of the power 
supply. Push down the tab to hold the cable clamp in 
place. See Fig. 24.
M2422B
ELECTRONIC
AIR CLEANER
POWER BOX
POWER BOX
SECURING
SCREWS (5)
POWER BOX COVER
POWER BOX COVER
SECURING SCREWS (5)
NOTE: SCREWS ONLY NEED TO BE
 LOOSENED, NOT REMOVED.