Install Instructions
PS1202C, PS2402C REPLACEMENT POWER SUPPLY KITS FOR ELECTRONIC AIR CLEANERS
69-1137EF—01 2
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition such as electrical shock.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
WARNING
Electric Shock Hazard.
Safety Hazard.
Can cause electrical shock or equipment 
damage.
Disconnect power before removing old power 
supply board and installing replacement power 
supply board. When servicing the F57 or F90, 
stand on a stable work platform or ladder.
Fig. 1. Power supply location on F50E Two-Cell Air 
Cleaners.
To Remove Old Power Supply 
Board And Performance Indicator 
Board
NOTE: It is advisable to observe the location of lead-
wires on the power supply to be replaced. 
Tagging the lead-wires as they are removed 
will help to correctly reconnect them.
 Open access door or grille. See Fig. 1 through 5.
 Open power box.
 Remove W8600E terminal block and wiring. Save 
screws for future use.
 On the F90, remove the power supply assembly as 
follows:
— Open the cover by pulling the two latches located 
on the front of the cover and swinging the cover 
down until it hangs (see Fig. 5).
— Remove the two prefilters and the two cells from 
the channel guides.
— Loosen the screws holding the power supply 
assembly cover plate and remove the cover plate. 
See Fig. 6.
— Loosen the two screws on the inner wall of the 
power supply assembly and three screws on the 
top of the assembly. Slide the power supply 
assembly toward the center of the air cleaner and 
disconnect the two Molex connectors and the one 
quick connect connector. See Fig. 6.
— Remove the power supply assembly to a table or 
work bench to replace the power supply.
 Disconnect the red ionizer and black collector leads at 
the board quick connects.
 Disconnect remaining input leads at the quick 
connects.
 Remove and set aside the sheet metal screws holding 
the power supply board in place. Remove the 
performance indicator board by clipping the four plastic 
standoffs with diagonal cutters, or squeezing the ends 
of the standoffs to release the board. Remove and 
discard the board.
M33489
2
ONE-CELL MODEL
1