Installation Sheet
TRUEZONE ARD, EARD, AND ZD SERIES DAMPERS
33-00040—03 4
WIRING
CAUTION
Personal Electrical Shock Hazard. Can cause
electrical shock or equipment damage.
Disconnect power before beginning installation.
The damper motor has a 24 Vac, 50/60 cycle, 8 VA rating.
The spring-return ARD and ZD damper requires 24 Vac to
M1 and M6 to power the damper closed. The damper then
returns to its normal open position once power is removed.
EARD damper requires 24 Vac to the two vent terminals to
power the damper open. The damper then returns to its
normal closed position once power is removed.
NOTE: Multiple dampers can be wired in parallel.
Wiring a Motor
See Fig. 6 for motor wiring hookups for ARD and ZD
Dampers.
Changing Motor on ARD, EARD and
ZD Dampers
1. Disconnect the motor wiring.
2. Loosen the socket head cap set screw located
between the faceplate and the motor coupling.
3. Remove the motor.
4. For ARD and ZD models: Ensure damper blade is in
the open position.
For EARD models: Ensure damper blade is in the
closed position.
5. Attach new motor to the coupling; be sure the
standoff on motor is positioned in the grommet on
the faceplate and the set screw is aligned with the
motor shaft hole.
6. Tighten the set screw.
Wiring an EARD to a W8150
Fig. 3. EARD and W8150 wiring.
WCR
C
RYG
AT120
W8150A
EARD-6
HVAC
WCRC Y G
G
R
C
C
C
C
H
W
G
THERMOSTAT
R
C
DAMPER
AUX
REMOTE
M23547A