User's Manual

Installation FlexLine
23
4.10.3 Unused cable inlets
Seal unused cable inlets with approved 3/4” threaded stopping plugs.
4.11 Electrical connection
NOTE
Install the conduits according to the instructions provided by the
manufacturer.
Warning!
Cables must always comply with the defined cable specifications.
Warning!
- Minimum incoming wire cross section should be at least 0.2mm
2
and may consist of a single-, fine- or multi-wire. With the use of
wire with a cross section between t 0.2mm
2
and <0.5mm
2
, the
maximum current I [A] should be reduced to a maximum of I =
0.55A.
- With a minimum wire cross section of t 0.5mm
2
the maximum
current I should not be higher then 3A and may consist of a single-
, fine- or multi-wire.
NOTE
The field cabling entering the SmartConn box must be as short as
possible.
NOTE
Depending on the ambient temperature classification the cables
must be suitable for Ta > 70 °C.