User Manual
Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 26 Service Manual
6.3.3.6.6 Observed Density
See 6.3.3.6.5 - Vapour Room Pressure.
6.3.3.6.7 Ambient Temperature
1
bit 0 - P1 exceeds min. / max. trip
pressure
1 - P2 exceeds min. / max. trip pressure
2 - P3 exceeds min. / max. trip pressure
3 - Exceeding range P1
4 - Exceeding range P2
5 - Exceeding range P3
6 - one
7 - zero
2
bit 0 - Fail P1
1 - Fail P2
2 - Fail P1
3 - Manual P3 used
4 - Last valid P3 used
5 - Manual level used
6 - one
7 - zero
3
bit 0 - Last valid density used
1 - Manual density used
2 - High density alarm
3 - Low density used
4 - HTG level fail
5 - No previous store command
6 - one
7 - zero
4
bit 0 - Manual gas density used
1 - Level below LN
2 - Last valid level used
3 - Invalid level reading
4 - API underflow/overflow or negative
density
5 - zero
6 - one
7 - zero
Health
status
code
Meaning
2561 LOWEST_ELEMENT_OFFSET_NOT_COMMISSIONED
2562 MRT_ELEMENT_LENGTH_NOT_COMMISSIONED
2563 MEASUREMENT_TYPE_NOT_COMMISSIONED
2564 ELEMENT_TYPE_NOT_COMMISSIONED
2565 NUMBER_OF_ELEMENTS_NOT_COMMISSIONED
Vapour Room Pressure status Meaning