Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 25
such a way that an ASCII code for a character is generated. The 8-bits
ASCII coded character is placed in the Low byte of the register; the High
byte remains empty (zero).
6.3.3.6.5 Vapour Room Pressure
Five registers contain the bit-coded vapour room pressure and
observed density status. The status information is coded in such a way
that an ASCII code for a character is generated. The 8-bits ASCII coded
character is placed in the Low byte of the register; the High byte
remains empty (zero).
Vapour Room Temperature status Meaning
0
indicating the highest immersed
(spot)element of the temperature
element
1
bit 0 - General temperature fail
1 - Fail in average product temperature
2 - Fail in average vapour temperature
3 - Level exceeds lowest (spot)element
4 - Level exceeds highest (spot)element
5 - (Spot)element fail
6 - one
7 - zero
2
bit 0 - Last valid level used
1 - Manual level used
2 - Level time out
3 - Device not calibrated (MTT)
4 - Exceeding differential temp. range
(MTT)
5 - Out of specified temperature range
6 - one
7 - zero
3
bit 0 - No previous store command
1 - Alternative element selected (MRT)
2-5 - zero
6 - one
7 - zero
Vapour Room Pressure status Meaning
0
bit 0 - General option board fail
1 - Low level alarm
2 - Low low level alarm
3 - High level alarm
4 - High high level alarm
5 - Level time out
6 - one
7 - zero