6.3.3.6 Status Information
After being requested so by the host, the slave will return the relevant
status information. The following tables give the possible received
status bytes from the relevant registers, such as product level, product
temperature etc.
For a listing of ASCII codes, see 6.3.4.
6.3.3.6.1 Product Level
This register contains the bit-coded product level status. This status
information is coded in such a way that an ASCII code for a character is
generated. The ASCII characters are listed below.
6.3.3.6.2 Water Level
This register contains the bit-coded water level status. This status
information is coded in such a way that an ASCII code for a character is
generated. The ASCII characters are listed below.
6.3.3.6.3 Product Temperature
This register contains the bit-coded product temperature status. This
status information is coded in such a way that an ASCII code for a
character is generated. The ASCII characters are listed below.
6.3.3.6.4 Vapour Room Temperature
Four registers contains the bit-coded vapour room temperature status.
With exception of the first register, the status information is coded in
Product Level status Meaning
F invalid level data
C out of measuring range
B measurement blocked
Mwarning
? reduced accuracy
- valid product level
Water Level status Meaning
F invalid water alarm data
A water above probe warning
Z water below probe warning
- valid water level
Product Temperature status Meaning
F invalid temperature alarm data
T reduced accuracy
- valid data