User Manual
Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 19
6.3.3.5.2 Floating Point Format Gauge Data
Par.no.
Modbus
parameter
Modbus
address (hex)
Modbus
Address (dec)
Data type
No. of registers
Conversion
units
Interpretation
1 ProductLevel 0x1000 SD44097 floating
point
2METRES
FEET
INCHES
ProductLevelStatus 0x1002 44099 char 1 See 6.3.3.6.1
ProductLevelAlarms 0x1003 44100 char 1 See 6.3.3.6.13
2 WaterLevel 0x1004 SD44101 floating
point
2METRES
FEET
INCHES
WaterLevelStatus 0x1006 44103 char 1 See 6.3.3.6.2
3 ProductTemp 0x1007 SD44104 floating
point
2 CELSIUS
FAHRENHEIT
ProductTempStatus 0x1009 44106 char 1 See 6.3.3.6.3
4 VapRoomTemp 0x100A SD44107 floating
point
2 CELSIUS
FAHRENHEIT
VapRoomTempStatus 0x100C 44109..12 byte 4 See 6.3.3.6.4
5 VapRoomPress 0x1010 SD44113 floating
point
2PASCAL
KILO_PASCAL
PSI
VapRoomPressStatus 0x1012 44115..19 byte 5 See 6.3.3.6.5
6 ObsDensity 0x1017 SD44120 floating
point
2 KILOGRAM_PER_M3
POUNDS_PER_FT3
DEGREES_API
ObsDensityStatus 0x1019 44122..26 byte 5 See 6.3.3.6.6
7 Gauge Status 0x102A 44139 byte 1 See 6.3.3.6.14
8 Spot temperature 1 0x1200 SD44609 floating
point
2 CELSIUS
FAHRENHEIT
9 Spot temperature 1 pos. 0x1202 SD44611 floating
point
2METRES
FEET
INCHES
10 Spot temperature 2 0x1204 SD44613 floating
point
2 CELSIUS
FAHRENHEIT
11 Spot temperature 2 pos. 0x1206 SD44615 floating
point
2METRES
FEET