User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 17
FEET devide by 1000
INCHES devide by 100
36 Spot temperature 15 0x0238 SD40569 long 2 CELSIUS devide by 100
FAHRENHEIT devide by 100
37 Spot temperature 15 pos. 0x023A SD40571 long 2 METRES devide by 10000
FEET devide by 1000
INCHES devide by 100
38 Spot temperature 16 0x023C SD40573 long 2 CELSIUS devide by 100
FAHRENHEIT devide by 100
39 Spot temperature 16 pos. 0x023E SD40575 long 2 METRES devide by 10000
FEET devide by 1000
INCHES devide by 100
40 Ambient Temperature 0x0300 SD40769 long 2 CELSIUS devide by 100
FAHRENHEIT devide by 100
Ambient
TemperatureStatus
0x0302 40771 integer 1 See 6.3.3.6.7
41 Product Pressure 0x0303 SD40772 long 2 PASCAL multiply by 100
KILO_PASCAL devide by 1000
PSI devide by 1000
Product PressureStatus 0x0305 40774 byte 5 See 6.3.3.6.8
42 Hart Input Variable 1 0x030A SD40779 long 2 METRES devide by 10000
FEET devide by 1000
INCHES devide by 100
Hart Input Variable 1
Status
0x030C 40781 Integer 1 See 6.3.3.6.9
43 Hart Input Variable 2 0x030D SD40782 long 2 CELSIUS devide by 100
FAHRENHEIT devide by 100
Hart Input Variable 2
Status
0x030F 40784 Integer 1 See 6.3.3.6.9
44 Hart Input Variable 3 0x0310 SD40785 long 2 PASCAL multiply by 100
KILO_PASCAL devide by 1000
PSI devide by 1000
Hart Input Variable 3
status
0x0312 40787 Integer 1 See 6.3.3.6.9
45 Hart Input Variable 4 0x0313 SD40788 long 2 KILOGRAM_PER_M3 devide by 100
POUNDS_PER_FT3 devide by 10000
DEGREES_API devide by 1000
Hart Input Variable 4
status
0x0315 40790 Integer 1 See 6.3.3.6.9
46 Hart Input Variable 5 0x0316 SD40791 long 2 Free format devide by 100
Hart Input Variable 5
status
0x0318 40793 Integer 1 See 6.3.3.6.9
Par.no.
Modbus
parameter
Modbus
address (hex)
Modbus
Address (dec)
Data type
No. of registers
Conversion
units
Scaling
factor