Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 7
6.3.2 Specifications
System Specification:
• Typical TurnAround Delay (TAD) = 35 ms *
• Maximum TAD = 65 ms *
• Refresh rate of 32 FlexLines on one link = 5.76 sec * (@ scan rate
of 180 ms)
• Refresh rate of 32 FlexLines on one link = 4.80 sec * (free running
host mode: no scan rate setting)
Recommended minimum host settings:
• Time out >= 65 ms * (assuming time out measurement resets at
start of slave message)
• Scan rate >= 180 ms *
* Note: @ 100 register @ 19K2 baud