SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 162 Service Manual
6.11.5 Commissioning Check
☛ After having checked/set all before listed entities, make sure
the
[Board Commissioned], the [Product temperature Commissioned], the
[Vapour temperature Commissioned], and the [Ambient Temperature Commis-
sioned]
entities are <True>;
the [Board Health], the [Product temperature Health], the [Vapour temperature
Health]
, and the [Ambient Temperature Health] entities are <GOOD>.
For viewing the software version, the Engauge Generic tab can be
viewed; also a Reset board command can be issued here.
NOTE: In the SmartView situation, the Commissioning flag
must be ‘G’ and the Health flag must be ‘Y’.