User Manual
Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 157
6.11.4.4 Commissioning Parameters for All Types of Probes
6.11.4.4.1 Engauge *Product temperature* Tab
☛ The following entities can be set set by Engauge or SmartView for a
specific functioning of the FII-RTD module in an instrument. The
default values are available after initialization of the non-volatile
memory; so check each entity for its correctness.
Name Explanation Value Range Default
[Lowest element offset] The distance from tank zero
till the bottom of the probe
floating point number:
<-x.x .. +x.x>
<80.0>
[Number of elements] The number of elements
used
<1..6> <0>
[Element type] The type (material) of the
used RTDs
<Pt100 large + small>
<Ni191>
<PtCu100>
<Cu100>
<Cu90 enraf + beacon + weston/
solartron/nulectrohms>
<Sangamo MRT>
<Sangamo spot>
<No type>
[Measurement type] Selects RTDs, MPT, or
MRT.
<RTD 3wire>
<RTD 4wire>
<MPT>
<MRT>
<No type>
Name Explanation Value Range Default
[Product immersion depth] The minimum required
product level distance
above an element before
this element is taken into
account in the average
product temperature
calculation
floating point number:
<-x.x .. +x.x>
<0.5>
[Hysteresis]
This is a hysteresis
mechanism distance
around the switching points
of the elements that are
taken into account in the
calculation.
floating point number:
<-x.x .. +x.x>
<0.1>