6.11.2 Some Important Settings
The FII-RTD can be tailored to the need of the customer by a lot of
settings. See 6.11.4 - Commissioning.
Some important settings of the FII-RTD are listed below.
6.11.3 Some Important Features
Temperature calculations can be:
Standard (just simple averaging the spot temperatures).
Enhanced (averaging the spot temperatures and taking into
account the contribution of each spot in respect to its immersion).
Custom (as standard but then giving it a weighing factor).
A temperature-range check can be turned on. In this case, if spot
elements are out of range, a fail state results (if not skipped), see
FIGURE 6-41.
Setting Remarks
[Element type] Can consist of following types:
Pt100 large + small
Ni191
PtCu100
Cu100
Cu90 Enraf + Beacon + Weston/Solartron/Nulectrohms
Sangamo MRT
Sangamo spot
[Measurement type] Can be:
RTD 3-wire
RTD 4-wire
MPT
•MRT
[RTD configuration] Can be:
RTD1 in tank
RTD1 + RTD2 in tank
RTD1 in tank + RTD2 ambient
RTD1 ambient
[Gauge temperature scale] Can be:
IPTS-68
ITS-90
[Lowest element offset] This is the distance from tank bottom till lowest element
position
[Number of elements] Can be 1..6
[MPT sensor length] -