Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 152 Service Manual
6.11.2 Some Important Settings
The FII-RTD can be tailored to the need of the customer by a lot of
settings. See 6.11.4 - Commissioning.
Some important settings of the FII-RTD are listed below.
6.11.3 Some Important Features
Temperature calculations can be:
• Standard (just simple averaging the spot temperatures).
• Enhanced (averaging the spot temperatures and taking into
account the contribution of each spot in respect to its immersion).
• Custom (as standard but then giving it a weighing factor).
A temperature-range check can be turned on. In this case, if spot
elements are out of range, a fail state results (if not skipped), see
FIGURE 6-41.
Setting Remarks
[Element type] Can consist of following types:
• Pt100 large + small
• Ni191
• PtCu100
• Cu100
• Cu90 Enraf + Beacon + Weston/Solartron/Nulectrohms
• Sangamo MRT
• Sangamo spot
[Measurement type] Can be:
• RTD 3-wire
• RTD 4-wire
• MPT
•MRT
[RTD configuration] Can be:
• RTD1 in tank
• RTD1 + RTD2 in tank
• RTD1 in tank + RTD2 ambient
• RTD1 ambient
[Gauge temperature scale] Can be:
• IPTS-68
• ITS-90
[Lowest element offset] This is the distance from tank bottom till lowest element
position
[Number of elements] Can be 1..6
[MPT sensor length] -