User Manual
Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 150 Service Manual
6.10.4 Commissioning Check
☛ After having checked/set all before listed entities, make sure
the
[Board Commissioned], the [Product temperature Commissioned], the
[Vapour temperature Commissioned], and - if applicable - the [Water level
Commissioned]
entities are <True>;
the
[Board Health], the [Product temperature Health], the [Vapour temperature
Health]
, and - if applicable - the [Water level Health] entities are <GOOD>.
[Alarm test] Activates and selects at the
same time the Alarm test (if
enabled with the
[Alarm test
enable]
listed before, and the
4 alarm thresholds are
properly set).
[No Alarm]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
<No Alarm>
[Function identification]
The current module’s
function name. This
function is visible on the
SmartView display.
13 characters <Water level>
Name Explanation Value Range Default