User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 132 Service Manual
[HART SV unit code] Unit code for linked SV <UNIT_CODE_UNKNOWN> Function 1 Communication
(HART
communication)
[HART TV unit code] Unit code for linked TV <UNIT_CODE_UNKNOWN>
[HART QV unit code]
Unit code for linked QV <UNIT_CODE_UNKNOWN>
[Configuration changed
Counter]
Increments every time the
configuration is changed
<0>
[Device ID] Same as Enraf Serial
number. This is a unique
number to every board.
[Device Type] Device type registered with
the HART Communication
Foundation
<127>
[Manufacturer ID Number]
Manufacturer ID registered
with the HART
Communication Foundation
<148>
[Number of Preambles]
Number of preambles
required for a request from
the HART master
<7>
[Number of Response
Preambles]
Number of preambles in the
HCI-HAO response stream
<7>
[Fixed Current Value] Fixed analog output current
set by HART command 40
<0> Function 2 Sensor
(Analog Output)
[Loop Current Mode] If HART mode selected is
<Standard 4-20mA>, then it is
enabled.
If HART mode selected is
<Fixed 4-20mA>, then it is
disabled.
<Enabled>
[Percentage of Range] Percentage of current PV
with respect to the limits set
<0>
Name Explanation Default Value
Function
Part
Function