User Manual
Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 126 Service Manual
All the HART-compatible devices connected over the HART bus
must have different polling addresses. Multi-drop mode is supported
only in Passive mode of loop configuration. When the output current
mode is set to
Standard_4_20_MA, the polling address of the device
must be made zero.
When the device is not in multi-drop mode (
STANDARD_4_20_MA mode
selected) then the output current follows the changes in linked PV
value.
Scanning of each linked available PV, SV, TV and QV on the CAN-
bus with frequency of 1 Hz. That means all the available linked
variables are scanned every 1 second.
The analog output is refreshed every 1 second, even if there is no
change in the scanned variables. So, the watchdog for analog output
is automatically implemented. If the output is not refreshed within 45
seconds then a watchdog to analog output is generated and the
output is forced to 0 mA.
During startup, the analog output of the HCI-HAO module is kept low
(< 0.5 mA). This value will be there till initialization takes place. Once
the normal operation starts the output will follow the linked PV
depending upon the output mode setting.
Manual overwrite mechanism. This is a standard FlexConn func-
tionality. Separate configuration and command entities are defined
for this. See 6.9.5 - Board Commissioning.
6.9.4 Calibration of the HCI-HAO
A calibration provision is given, which is used to accurately map the
analog output between 4 -20 mA using the two range values entered for
Primary Variable.
Following table lists all entities required for calibration.
NOTE: Commands used in the following calibration
procedure can be executed either by using the CAN
tool, the SmartView, or Engauge.
Calibrate the analog output of the HCI-HAO as follows:
☛ Connect loop resistor at connector CN2
☛ Power up HCI-HAO board
Entity Data Type Type
[Analog Output at 4 mA] Float non-volatile R/W
[Analog Output at 18 mA] Float non-volatile R/W
[Calibrate at 4 mA] Undefined command
[Calibrate at 18 mA] Undefined command
[Enter Calibration Mode] Undefined command
[Exit Calibration Mode] Undefined command