User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 118 Service Manual
TABLE 6-15 Function 1 commissioning entities
6.8.4.2 Function 2 Commissioning
Set all Function 2 entities according to TABLE 6-16 requirements, to
commission P3.
TABLE 6-16 Function 2 commissioning entities
6.8.4.3 Function 3 through 7 Commissioning
Set all Function 3 through 7 entities according to TABLE 6-17
requirements, to commission all generic HART sensors.
<Disabled> Yes [P1 ambient air pressure] z <default>
AND
[P1 installed] = <enable>
<True>
[P1 ambient air pressure]
= <default>
OR
[P1 installed] = <disable>
<False>
No N/A <True>
HIMS
Density
P3 Pressure
Sensor
Detected
P3 Installed P3 Ambient Air Pressure Commissioned
<Enabled> Ye s <Enable> [P3 ambient air pressure]
z <default>
<True>
[P3 ambient air pressure]
=
<default>
<False>
<Disable>
N/A <False>
No <Enable> N/A <False>
<Disable> <True>
<Disabled>
Yes <Enable> [P3 ambient air pressure]
z <default>
<True>
<Disable> [P3 ambient air pressure]
z <default>
<False>
N/A [P3 ambient air pressure]
=
<default>
<False>
No N/A N/A <True>
HIMS
Density
P1 Pressure
Sensor
Detected
P1 Ambient Air Pressure and P1 Installed Commissioned