User Manual
Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 113
TABLE 6-7 Accepted units for generic HART devices
If an accepted HART PV unit code is found, the HART device is
allocated to the relevant FlexConn function as detailed in TABLE 6-8.
If the HART PV unit code is not accepted, the HART SV unit code is
checked against TABLE 6-7 in the following order: Distance,
Temperature, Pressure, and Density. If an accepted HART SV unit
code is found, the HART device is allocated to the relevant FlexConn
function as detailed in TABLE 6-8.
The process is repeated for the HART TV unit code.
If none of the unit codes are accepted, the device is allocated to
Function 7.
☛ If a generic HART device output is not in the accepted units,
configure it to accepted units output data, by using the HART config-
uration tool.
TABLE 6-8 FlexConn function allocation
Once a device has been allocated to a function, the HART PV, SV, and
TV are translated into the FlexConn function’s PV, SV, and TV.
The required sensor value of the generic HART device may not be in
the HART PV but it is translated into the FlexConn PV.
Example:
Temperature Degrees Celsius °C 32
Degrees Fahrenheit °F 33
Distance Feet ft 44
Meters m 45
Inches in 47
Density Kilograms per cubic meter kg/m
3
92
Pounds per cubic foot lb/ft
3
94
Degrees API API 104
FlexConn Function Device Type
Function 1
[P1 Pressure]
Function 2 [P3 Pressure]
Function 3 [Distance]
Function 4 [Temperature]
Function 5 [Pressure]
Function 6 [Density]
Function 7 [Other]
Function 8 [HIMS Density]
Sensor Type Accepted HART Units Abbreviation
HART Unit
Code