Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 107
In analog mode, the connected HART device will be allocated to
Function 1 through 7, depending on the type of HART device
connected.
FIGURE 6-30 Analog mode system diagram
6.8.3 Software Specifications
6.8.3.1 General
The main function of the FCI-HT software is to measure HIMS product
density, by connecting the FCI-HT board via the HART bus to 2
pressure sensors (P1 and P3), and via the FlexConn bus to a product
level sensor and an optional water level sensor.
The alternative function is to connect up to 5 generic HART devices
operating in multi-drop digital mode, or 1 generic HART device
operating in analog mode.
The FCI-HT software only supports HART devices with the following
addresses.
HART Address Function
00 Reserved for HART device in analog mode
01 Reserved for P1 pressure sensor
02 N/A Reserved for future use
03 Reserved for P3 pressure sensor
04 HART generic sensor
1
CAN-Bus
FCI-HT
Generic
HART