User Manual
Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 101
So, for example, if a stand-alone SmartView (address 3) and an
integrated SmartView (address 2) are connected, the stand-alone
SmartView (address 3) will be served as soon as the integrated
SmartView (address 2) is closed (set to idle).
6.7.2 Commissioning the FII-SMV
For a correct functioning of the FII-SMV module in an instrument the
following entities can be set by using either Engauge or SmartView.
☛ By using the following table, check each entity for correctness.
Name Value Range Default Value Explanation
[Decimal separator] <point>
<comma>
<point> The decimal separator in
which entities are shown on
the SmartView display.
[Tenth millimeter selection] <enable>
<disable>
<enable> Determines whether the
tenth millimeter is shown on
the display in the
[PV screen]
in case a level entity is
shown.
[Identification] 8 characters e.g.
<TANK1234>
<-------->
Name of a tank or
instrument. This string is
visible within a [PV screen].
[Password] <......> 6 characters <ENRAF2> The password SmartView
uses for entering the
protected level.
Note: Some settings reside
under the protected level.
[Function identification] <......> 13 characters <SmartView mst> The name of the current
function of this module.
This name is visible on the
SmartView display.
[Extra information switch] <level temperature>
<Info Switch>
<Info Switch> Determines whether the
[extra information] screen on
the SmartView will display
level and temperature or
extra information from a
specific function.
[Extra info board ID] <01......XX> 2 digits <01> Board ID of the board that
has the
[extra information] to
display.
In case of OneWireless, the
ID = 12.
[Extra info board instance] <00......XX> 2 digits <00> Board instance of the board
that has the
[extra information]
to display.
[Extra info function instance] <01......XX> 2 digits <01> Function instance that has
extra information to display.
In case of OneWireless,
this = 01.