User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 101
So, for example, if a stand-alone SmartView (address 3) and an
integrated SmartView (address 2) are connected, the stand-alone
SmartView (address 3) will be served as soon as the integrated
SmartView (address 2) is closed (set to idle).
6.7.2 Commissioning the FII-SMV
For a correct functioning of the FII-SMV module in an instrument the
following entities can be set by using either Engauge or SmartView.
By using the following table, check each entity for correctness.
Name Value Range Default Value Explanation
[Decimal separator] <point>
<comma>
<point> The decimal separator in
which entities are shown on
the SmartView display.
[Tenth millimeter selection] <enable>
<disable>
<enable> Determines whether the
tenth millimeter is shown on
the display in the
[PV screen]
in case a level entity is
shown.
[Identification] 8 characters e.g.
<TANK1234>
<-------->
Name of a tank or
instrument. This string is
visible within a [PV screen].
[Password] <......> 6 characters <ENRAF2> The password SmartView
uses for entering the
protected level.
Note: Some settings reside
under the protected level.
[Function identification] <......> 13 characters <SmartView mst> The name of the current
function of this module.
This name is visible on the
SmartView display.
[Extra information switch] <level temperature>
<Info Switch>
<Info Switch> Determines whether the
[extra information] screen on
the SmartView will display
level and temperature or
extra information from a
specific function.
[Extra info board ID] <01......XX> 2 digits <01> Board ID of the board that
has the
[extra information] to
display.
In case of OneWireless, the
ID = 12.
[Extra info board instance] <00......XX> 2 digits <00> Board instance of the board
that has the
[extra information]
to display.
[Extra info function instance] <01......XX> 2 digits <01> Function instance that has
extra information to display.
In case of OneWireless,
this = 01.