In other words, this means: In case an anomaly is deteced by the
internal gauge diagnostics, the gauge needs service within the time
set by this timer.
Typical value:
<72> hours.
If the Safety shut down time is disabled, so value =
<0>, then the
customer wants to continue permanently with the other branch.
NOTE: When the "Safety shut down timer" is active or
running, the remaining time until shutdown can be
inspected by reading the
[Safety shut down timer left]
entity.
6.6.11.7.2 TII-XR
Set the
[Overfill Protection Function] entity to <Enabled>.
Set the [First Relay Board Instance] entity of the [Board Instance] entity to
the first FII-DO board.
Set the
[Second Relay Board Instance] entity of the [Board Instance] entity to
the second FII-DO board.
The "Maximum Safe Fill" mechanism of the TII-XR should be ignored
for the SmartRadar FlexLine overfill protection application.
When the "Maximum Safe Fill" level is configured lower than the Over
fill Threshold, the PV status becomes BAD much earlier, and the FII-DO
will open the contacts.
Set the [Maximum safe fill level] entity above the [Threshold] values of the
FII-DO boards when used for overfill protection.
OR
Set the 9th switch
[Compensations and features] entity to <FALSE>.
6.6.11.7.3 PSX (Power Supply)
CAUTION! The Overfill Protection Application may ONLY be
powered by AC mains. Only 85VAC - 240 VAC can
be used for mains connected to the SmartRadar
FlexLine having the Overfill Protection Application
option.