Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 96 Service Manual
6.6.11.6 Overfill Protection Application Wiring
Connect the external wiring (see illustrations below):
Connect terminal 48 to the pump or to the valve.
Connect terminal 49 to the mains.
6.6.11.7 Commissioning the Overfill Protection Application
To configure the Overfill Protection Application all essential boards
needs to be configured.
6.6.11.7.1 FII-DO (redundant)
Make sure all jumpers are set to Normally Open (N.O.). See 6.6.3.1.
Set the
[Board Instance] entity of each FII-DO board to a different value
(e.g. 0 and 1).
The boards are redundant and share the same board ID, so to be
able to address the board uniquely by the internal (CAN-bus) or
external FlexConn protocol, the board instance must be different to
distinguish the boards from each other.
Set the
[Counterpart Board Instance] entity of each FII-DO board to the
[Board instance] of the counterpart FII-DO board (redundant board).