User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 92 Service Manual
The relays must be set to Normally Open (jumper, see 6.6.3.1) and
Normally Energized (configuration parameter, see 6.6.3.2).
In a normal situation, the relay contacts are closed.
Relays 4 are used to increase the availability: if a problem is
detected with the other relays, the redundancy takes care that the
overfill protection function will work (see also FIGURE 6-23).
The relays typically can stop a pump or close a valve that is used
filling a storage tank. See FIGURE 6-23.
Overfill safety analysis, including diagnostic tests is done every
second.
The 2 FII-DO boards are continuously checking each other for a
correct functioning. This is done every second. In case of
malfunction, 2 retries are executed before the status is definitely
determined.
The radar scans the overfill protection status every second and will
react accordingly.
6.6.11.4 Overfill Protection Board Actions
The following table shows the important parameters for overfill
protection.
Both board contacts are always opened if one out of the following
events occurs:
Level = 0 (product level >= threshold, product level TV = BAD/
UNCERTAIN, TII-XR board does not respond)
Voltage = 0 (one of more board voltages out of range)
Board diagnostic = 0 (board status = BAD / UNCERTAIN)
Board diagnostic of counter part (redundant board) = 0 (board
status = BAD / UNCERTAIN)
Counter part (redundant board) communication = 0 (other
relay board does not respond)
Output = Function PV
1 = relay contact closed
0 = relay contact opened (safe situation)
Diagnostics = Function health + Board health
1 = status = GOOD, healthy
0 = status = BAD, UNCERTAIN, not healthy (force safe situation)
Level = product level analysis
1 = product level < threshold
0 = product level >= threshold (force safe situation)
0 = product level status = BAD, UNCERTAIN, not healthy
0 = no communication with the TII-XR
Voltage = all FlexConn monitored voltages
1 = voltage within specifications (OK)
0 = voltage too high (one or more) (force safe situation)
Counter part communication = communication with other relay board
1 = valid communication
0 = no communication (force safe situation)