User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 89
6.6.9 Board Commissioned Entity
The
[Board Commissioned] entity will display either <True> if all functions are
commissioned or
<False> if any of the functions are not commissioned.
If the
[Board Commissioned] entity displays <False>, check each function
parameter again. Use the table from 6.6.8.
6.6.10 Fail-safe Level Application
Following steps include all commissioning-aspects settings for the Fail-
safe level application.
The corresponding jumper of the concerned relay must be in the
Normally Open (NO) state (= default setting).
NOTE: In the Commissioning stage, no jumper setting can
be changed without breaking the compartment screw
sealing. See also section 6.6.3.1.
Set
[Operation Mode] to [Alarm Mode].
Set [Relay Mode] to <Energized>.
Set [Alarm Mode] to [PV Monitor].
Set
[Monitor Board ID] to <board id> of product-level board.
Set [Monitor Board Instance] to <board instance> of related product-level
board.
Set
[Monitor Function Instance] to <function instance> of related product-
level board.
Set [Monitor Source] to <PV>.
Set
[Monitor Mode] to [Remote].
Set
[Remote Threshold Source] to <HH>, <HA>, <LA>, or <LL>.
Set corresponding alarm setting of the related product-level board.
Set
[Status Behavior] to <BAD-UNCERTAIN>