User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 86 Service Manual
Activate
Deactivate
Acknowledge
6.6.5.1 Activate
The
!Activate! command will cause the specified relay to become
<Activated>. This command is only available in [Remote Control] mode; see
6.6.4.2.
The
!Activate! command behavior is modified by the [Time Setting] entity. If
the
[Time Setting] entity is set to zero, the relay will stay permanently
activated until a
!Deactivate! command is given.
If the
[Time Setting] entity is set to a value other than zero, the relay will be
activated for a time in seconds equal to the value set in the
[Time Setting]
entity, then deactivated. During the period the relay is activated, the
relay state will be
!Time Setting Active!. This is useful for site
commissioning.
For each relay, set the
[Time Setting] entity to the desired value.
6.6.5.2 Deactivate
The !Deactivate! command will cause the specified relay to become
<Deactivated>. This command is only available in [Remote Control] mode;
see 6.6.4.2.
6.6.5.3 Acknowledge
The
!Acknowledge! command will cause the specified relay to be
physically deactivated, but the relay status will be set to
!Acknowledged!.
This command is only available in
[PV Monitor] mode; see 6.6.4.1. This
command can only be given when the concerned relay has already
been activated.
For example, this command is useful if the relay is connected to an
alarm system. The alarm can be silenced by the command, but it is still
possible to determine if an alarm has occurred. When the alarm
condition is then removed, the relay state will become deactivated, and
normal operation will resume.
6.6.6 LED Association
Depending on the value set in the
[LED Association] entity, the 4 individual
relays on the FII-DO board can be associated with one out of 2 LEDs,
LE2 or LE3 (see FIGURE 6-19).
The associated LED will be ON when the relay state is
<Activated>, and
the LED will be OFF when the relay state is
<Deactivated>.