User Manual
Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 85
NOTE: This behavior takes priority over the [Remote] or
[Local] monitoring. For example: If the [Status
Behavior]
is set to <BAD>, and the scanned PV or SV
health is Bad, the respective relay will be activated
regardless of the
[Monitor Mode] entity settings. The
[Remote] or [Local] option PV or SV checks will then
not affect the relay status.
6.6.4.2 Remote Control
In
[Remote Control] mode, each individual relay can directly be activated or
deactivated, by sending an
!Activate! respectively a !Deactivate! command
via the CAN bus.
The behavior of each individual relay is further controlled by the
[Remote
Control]
mode entity, which can be set to either <Restricted> or <Not
Restricted>
.
If the
[Remote Control] mode entity is set to <Not Restricted>, any source
can be used to control the relay with an
!Activate! or a !Deactivate!
command.
If the [Remote Control] mode entity is set to <Restricted>, the relay can
only be controlled by the source that matches the values set in the
[Control Board ID], the [Control Board Instance], and the [Control Function
Instance]
.
☛ From the
[Remote Control] mode menu, select either <Restricted> or <Not
Restricted>
.
☛ If Not Restricted was selected, skip to 6.6.4.3.
☛ Select
[Control Board ID], set proper value.
☛ Select [Control Board Instance], set proper value.
☛ Select
[Control Function Instance], set proper value.
6.6.4.3 Not in Use
If an individual relay is not required in a particular application, the
[Alarm
Mode]
entity must be set to <Not In Use>.
Example: If a particular application requires only two relays to be used,
say relay 1 and 2, then for relay 3 and 4 the
[Alarm Mode] entities must be
set to
<Not In Use>.
☛ For the FII-DO relays not used within the application, set the
[Alarm
Mode]
entities to <Not In Use>.
6.6.5 Commands
The following commands can be given to the FII-DO: