User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 84 Service Manual
6.6.4.1.1 Monitor Mode
The
[Monitor Mode] entity can either be set to [Remote] or [Local].
If the
[Monitor Mode] is set to [Remote], the alarm status of the scanned
PV or SV is monitored. The alarm status is compared against the
value set in the
[Remote Threshold Source] entity. The [Remote Threshold
Source]
entity can be set to <HH>, <HA>, <LA>, or <LL>.
Example: If the
[Remote Threshold Source] is set to <HH> and a High High
Alarm occurs, the relay will be activated. It will not be activated by any
other alarms.
If
[Local] [Monitor Mode] is to be set, skip to next bullet ().
From the [Monitor Mode], select [Remote].
Select
[Remote Threshold Source], set desired value.
If the
[Monitor Mode] is set to [Local], the scanned PV or SV value is
compared against the value set in the
[Threshold] entity. The behavior
is modified by the
[Threshold Mode] and the [Hysteresis] entities. The
[Threshold Mode] entity can be set to either <Treat as HA> or <Treat as LA>.
If the
[Threshold Mode] entity is set to <Treat as HA>, the relay is activated
if the scanned PV or SV is greater than or equal to the
[Threshold]
entity value, and the relay is deactivated if the scanned PV or SV is
less than the
[Threshold] entity value minus the [Hysteresis] entity value.
If the
[Threshold Mode] entity is set to <Treat as LA>, the relay is activated
if the scanned PV or SV is greater than or equal to the
[Threshold]
entity value, and the relay is deactivated if the scanned PV or SV is
less than the
[Threshold] entity value plus the [Hysteresis] entity value.
From the [Monitor Mode], select [Local].
Select [Threshold Mode], and choose either <Treat as HA> or <Treat as LA>.
Select
[Hysteresis], set desired value.
6.6.4.1.2 Status Behavior
The Status Behavior entity determines what happens to the relay if the
health of the scanned PV or SV differs from Good. The
[Status Behavior]
should be set to one of the following options: <BAD>, <BAD-UNCERTAIN>,
or
<Not Used>.
If the
[Status Behavior] is set to <BAD>, and the scanned PV or SV
health is Bad, the respective relay will be activated.
If the
[Status Behavior] is set to <BAD-UNCERTAIN>, and the scanned PV
or SV health is Bad or Uncertain, the respective relay will be
activated.
If the
[Status Behavior] is set to <Not Used>, the respective relay will not
be activated if the scanned PV or SV health is Bad or Uncertain.
Set the [Status Behavior] entity either to <BAD>, <BAD-UNCERTAIN>, or
<Not Used>.