Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 71
6.5.2.4 Alarm Settings
Set the entities [High high alarm], [High alarm], [Low alarm], [Low low alarm],
and
[Alarm hysteresis] to the desired values.
For definitions, see FIGURE 6-10
ESF07-0012
FIGURE 6-10 Alarm and hysteresis definitions
All above mentioned entities MUST be set as the defaults are
extremes (1E+12). If they are not, no errors will be displayed, but the
[Commissioned] entity will be <False>.
If the alarm entities are correctly set, but the [Alarm hysteresis] is not,
then any alarms that would raise will never be set off! So watch the
[Commissioned] status.
Be aware that the alarm status is only visible in the [Primary value]
entity (innage)! It is not visible in the [Secondary value] entity (ullage).
Although the GPU-protocol always contains the alarm status, the
current software only passes the actual alarm status to this protocol if
the gauge is set to innage control. So when ullage status is asked for
by the GPU-protocol, NO alarm statuses are displayed.
Workaround solution: Set the GPU records to innage.
Tank zero
Alarm Hysteresis
Alarm Hysteresis
Maximum safe fill
High High alarm
High Alarm
Low Alarm
Low Low alarm