User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 70 Service Manual
ESF07-0009
FIGURE 6-9 Level check entities
NOTE: This command does not adjust the
[Tank bottom
position]
, so this entity should be set manually to
approximately the correct value (within ± 0.1 m).
Give the [Accept reference] command.
Make sure the [Accept reference status] is <GOOD>.
Some remarks for the Engauge users:
To make sure the
[Accept reference] command works fine, all entities
must have been sent to the gauge (no yellow backgrounds may be
visible) prior to giving the command.
To read the
[Accept reference status], push the [Read] button (is not auto-
matically displayed).
Some remarks for the SmartView users:
On the SmartView display, the advanced entity
[Reference radar] is
visible as well. The value of this entity must be left to the default
value <+999.9999>.
Check [Reference status] in the commissioning menu, to see if the
command has been accepted.
Reference innage
Radar reference
Tank bottom position
Reference ullage
Upper reference position
Tank zero (dipping plate)