User Manual

Commissioning
SmartRadar FlexLine Part No.: 4417.762_Rev07
6 - 58 Service Manual
For a correct functioning of the HCI-GPU module in an instrument
(gauge), the following entities can be set by using either Engauge or
SmartView.
By using the following table, check each entity for correctness.
Name Value Range Default Value Explanation
[Identification] 8 characters e.g.
<TANK1234>
<-------->
Name of a tank or
instrument
[GPU instrument address] <0..99> <0> The address of this
instrument for GPU
messages.
Note: Each instrument must
have a unique GPU
address.
[GPU Caching]
<caching off>
<GPU B record>
<GPU C record>
<GPU D record>
<GPU L record>
<GPU M record>
<caching off> By switching on caching,
the system performance
can be greatly improved.
Switching caching on for a
record means that the
OneWireless network will
automatically keep an up-
to-date copy of this record
in the internal cache of the
gateway. This copy will be
refreshed each second.
Any request for this record
will NOT be sent to the
instrument but directly be
answered from the cache.
Note: Do not use this
setting for W&M approved
systems.
[FlexConn instrument address] <0..1899> <0> The address of this
instrument for FlexConn
messages.
Note: Each instrument must
have a unique FlexConn
address.
[Level units] <meters>
<inches>
<feet>
<fractions>
<meters> The unit in which level-
related GPU records and
items are shown
[Temperature units] <celsius>
<fahrenheit>
<celsius> The unit in which
temperature-related GPU
records and items are
shown