User Manual

Commissioning
Part No.: 4417.762_Rev07 SmartRadar FlexLine
Service Manual 6 - 57
All 4 configurable transducer blocks have the same settings in
Engauge. However the various configurable transducer blocks are
reserved for particular types of data:
Configurable Transducer block 1 is reserved for level data
Configurable Transducer block 2 is reserved for temperature data
Configurable Transducer block 3 is reserved for density and pressure
data
Configurable Transducer block 4 can be used for any of the data
types mentioned above.
The Secondary Variable (SV) of the configurable function block is
automatically assigned to the Secondary Value of the FlexConn board
function that is linked to the Primary Variable PV as described before.
6.4.7 Commissioning the HCI-1WL for GPU and FlexConn Communication
By using a protocol tunnel through the OneWireless network, it is
possible to connect the standard Honeywell Enraf Entis systems, or
service tools.
The physical connection between the Entis systems or service tools is
either via an Ethernet connection to the Gateway, or via an RS-232 line
through a Lantronix RS-to-Ethernet convertor to the Gateway. See
chapter 4.2.1 for details.
[Function Instance] This identifies the function
which data you want to map
to this transducer block.
<0...15> <0>
[Unit Type]
The unit type is necessary
to identify in One Wireless.
<0...5> <0>
units of data:
0 = no unit
1 = level
2 = temperature
3 = pressure
4 = density
5 = current
Example
To link a configurable transducer block to the Radar Level of
the TII-XR, the following settings need to be configured:
[Board ID] = 5
[Board instance] = 0
[Function instance] = 1
[Unit type] = 1
Name Explanation Value Range Default