Firmware Upgrade - Upgrading the Wireless Field Interface device
Part No.: Rev01 Wireless Field Interface
User’s Manual 3 - 3
3.3 Upgrading the Wireless Field Interface device firmware
The devices at the farthest hop level must be upgraded first.
CAN-1WL FlexConn board firmare
1. On the Selection Panel of the OneWireless user interface, select the
field device.
You can select multiple devices of the same type using the Selection
Panel or the map view. Use SHIFT +click to select multiple items in a
successive list. Use CTRL+click to select multiple items not in
succession.
2. On the ribbon bar, in the Upgrade group, click Application. The
Application Firmware Upgrade dialog box appears.
3. In the Available Firmware Files list, select the required firmware
upgrade files.
By default, the firmware upgrade file appears in the list. If the file is
not available in the list, perform the following steps to open the
firmware file.
a)
Click Add to browse to the directory location of the firmware upgrade file.
b) Click Open.
4. Click Upgrade.
The Application Firmware Upgrade dialog box appears.
The Firmware Upgrade Status dialog box displaying the status of
the upgrade appears. Closing the dialog box allows the upgrade
operation to run in the background. The upgrade status is displayed
in the status bar. Click the firmware upgrade status box to open the
dialog box again. If multiple users are simultaneously upgrading
different device firmware, all the users can view the progress of all
the device upgrades.
5. Close the Firmware Upgrade Status dialog box.
6. Verify the upgraded version of the firmware is as follows:
a) On the Selection Panel of the OneWireless user interface, select
the field device.
b) On the Property Panel, expand Device Manager Summary.
c) Under Identification group, review the firmware version
displayed in the Sensor Revision field.