Configuration - Configuring the protocol tunneling
Part No.: Rev01 Wireless Field Interface
User’s Manual 2 - 27
2.3.3.3 Configure Standard Serial Tunnel settings on the Lantronix device
Configure Standard Serial Tunnel firmware to enable it to properly
tunnel Wireless Field Interface device messages from the RS-232 serial
port to the Ethernet port of the WDM.
To configure Standard Serial Tunnel settings on the Lantronix device
1.
From the Start menu, open Lantronix DeviceInstaller.
2. In the Lantronix Devices tree on the left pane, select the Lantronix Xpress-
DR or Lantronix Xpress-DR-IAP device name.
3. On the Telnet Configuration tab, click Connect.
4. When prompted, press Enter to go to the setup mode.
5. On the Main menu, press 1 on the keyboard to configure channel 1 and set
the configuration parameters as follows:
Baud Rate = 19200
I/F Mode = 4C
Flow = 00
Port Number = 34568
Connect Mode = CC
Datagram Mode = 01
The Remote IP Address can be entered only when the Datagram
Mode is set to 01.
Remote IP Address = IP Address of the WDM
Remote Port = 55598
Packet Control = 00
Send Character 1 = 00
Send Character 2 = 00
6. Press 9 on the keyboard, to save and exit the Lantronix main menu.