User's Manual

Table Of Contents
Configuration - Configuring Wireless Field Interface device
Part No.: Rev01 Wireless Field Interface
User’s Manual 2 - 15
Routing Enabled — Enables the routing field device to function as a
router and an I/O device. The default join policy configured is Follow
System Manager Policy.
Not Applicable
– Does not apply to devices that are capable of operating as
access points.
– Does not apply to devices that are only capable of operating as
routers.
4.
Select one of the following Join Assignment options, as required.
The Join Assignment overrides the system manager join policy. This is
applicable only for routing field devices.
Join Disabled — Disables device-join through this device.
Join Enabled — Enables device-join through this device.
Follow System Manager Policy — Enables the device to follow the
system manager join policy. Device-join through this device depends
on the configured system manager join policy.
The Join Status is a read-only parameter that indicates the resultant join
state for all the devices.
Access Points, FDAP access points, and FDAP routers have the
Join Assignment permanently set to Join Enabled.
Non-routing field devices have the Join Assignment permanently
set to Join Disabled.
Routing field devices have the default Join Assignment set to
Follow System Manager Policy.
By default, the selected Wireless Field Interface devices are provisioned
and joined as line powered routers. Select Device Management > Routing
Assignment > Routing Disabled to disable the routing field devices to
function as line powered routers.
5. Click Apply.
2.2.3 Configuring Wireless Field Interface device channels
2.2.3.1 Configure Mode and Scale
To configure Scale
1.
On the Selection Panel, select the Wireless Field Interface device channel.
2. On the Property Panel, expand Process Variable to view the following
read-only parameters in the OneWireless user interface.
WARNING!
The configuration of the engineering units should be
performed using the Engauge tool only. The parameter values
of the sensor cards get reflected in the OneWireless user
interface as read-only parameters.
EU at 100%: Specifies the high range PV value in Engineering Units.
EU at 0%: Specifies the low range PV value in Engineering Units.