Tank zero
UR
Commissioning
Page 30
Figure 3.11 Upper reference value
3.4.6 Ullage readout
The two items described in this section need only be programmed, when ullage readout is required.
Refer to figure 3.11.
Item Name Description
W2
= Protection level 2 Enter password 2 (default password: ENRAF2)
UR
= Upper reference Format according to item
LD
.
The upper reference value is only used when 'Ullage' is to be
read from the 973 SmartRadar LT gauge. The ullage is then
calculated as: UR - 973 measured level
DE
= Level type One ASCII character.
DE = I for innage (default setting)
DE = U for ullage
EX
Exit Exit protection level