Commissioning
Instruction manual 973 SmartRadar LT Page 27
Figure 3.8 Example of determining the position of an obstruction zone
Figure 3.8 shows a Reflection Diagram in which an obstruction is found at approximately 8 m level
(6.25 m ullage). The product reflection is found at approximately 3.8 m level (10.44 m ullage).
In this example, the following settings should be selected:
Obstruction zone start at 5.85 m
ullage
(at least 0.4 m before the obstruction reflection).
Obstruction zone end at 6.65 m
ullage
(at least 0.4 m after the obstruction reflection).
Obstruction zone threshold at 5 dB.
Item Name Description
W2
= Protection level 2 Enter protection level 2
OS.0.1
= Obstruction zone 1 start Format according to item
LD
.
In the above example, obstruction zone 1 start should be
programmed as 5.85 m (OS.0.1=+005.8500)
OE.0.1
= Obstruction zone 1 end Format according to item
LD
.
In the above example, obstruction zone 1 end should be
programmed as 6.65 m (OE.0.1=+006.6500)
OT.0.1
= Obstruction zone 1 threshold Format according to standard power format (dB).
In the above example, the threshold of obstruction zone 1 is set
at 5 dB (OT.0.1=+0005.0)
OZ
= Enable / disable obstr. zones Ten ASCII characters; either E (enable) or D (disable) the
obstruction zone. For example: OZ=EDDDDDDDDD
enables the first obstruction zone
EX
Exit Exit protection level