Commissioning
Instruction manual 973 SmartRadar LT Page 19
3.4.1 Selecting dimension and decimal separator
When one or more dimension items are changed, all items with related formats will be automatically
changed and the values will be automatically converted to the new dimension. The same applies for the
decimal separator. The SmartRadar LT can be completely programmed in another dimension than it is
intended to operate in. Just change the item
LD
(and any other dimension items).
Item Name Description
W2
= Protection level 2 Enter password 2 (default password: ENRAF2)
LD
= Level dimension Selects and converts the level dimension. This item contains
one character, which can be:
M : metres; format: sign X X X separator X X X X
F : feet; format: sign X X X X separator X X X
I : inches; format: sign X X X X X separator X X
P : fractions; format: sign X X ' X X " X X
DP
= Decimal separator The item
DP
(decimal separator) can be:
.
: point or
, : comma.
EX
Exit Exit protection level
Standard formats
There are two standard formats; these formats are:
• Standard floating point format: sign point M M M M M M M M E sign P P
• Standard power format [dB]: sign X X X X point X
where: M = mantissa
P = exponent
X = value in decibel