User's Manual

Table Of Contents
PC
running
'Ensite'
a) RS-232C communication b) RS-485 communication c) HART communication
PC
running
'Ensite'
RS-232C
To one
SmartRadar LT
To one (or more)
SmartRadar LT
Host (RS-485)
RS-232C/
RS-485
converter
PC
running
'Ensite'
To one (or more)
SmartRadar LT
Host
(4-20 mA or HART )
®
RS-485
HART
®
HART
modem
®
250 W
RS-232C
File Edit= Search Instruments Options Windows Help 15:23:18
Baudrate
Baud
Baud
Baud
Baud
Baud
Baud
Baud
Baud
()
()
()
()
()
()
()
()
150
300
600
1200
2400
4800
9600
19200
Port
()
()
()
()
()
()
()
()
Com 1
Com 2
Com 3
Com 4
Com 5
Com 6
Com 7
Com 8
Parity
()
()
()
()
()
No
Odd
Even
Mark
Space
()
()
5
6
7
8
1
2
()
()
()
()
Databits Stopbit(s)
Communication dialog [ENSITE.ECS]
Communication- and protocolparameters
[]
Prefix:
Suffix:
<STX><CIU=0><TA=00><TOI=B><TOR=Z>
<ETX><BCC=1>
OKSafe Cancel
Timeout
Turn around delay
Retries
3500
0
3
(ms)
(ms)
Commissioning
Page 16
Figure 3.3 RS-232C / RS-485 and HART connections
3.3.4 Programming communication parameters
Start up the Ensite service tool and make contact with the SmartRadar LT to be configured. It is not
recommended to make a site scan, as the transmission address is still to be changed.
Therefore, to make contact with the gauge, set the address manually in the port settings. This is only
possible if the ExtendedSetup line in the ENSITE.ECS file (in subdirectory ECS) is set to: True.
Select this window by: Set up, Port settings, and go by mouse (or with the TAB key) to the Baud rate.
Select 1200 baud when communicating via Enraf field bus and HART ;
®
select 19200 baud when communicating via RS-232C or RS-485.
Select the used comport on the service PC.
Then go to the line: Prefix.
When communication via 858 or 880 CIUs, fill the desired CIU address (in the example above, it is 0).
When communicating via RS-232C / RS-485, default the CIU emulation address is disabled. Hence, delete
the part with the CIU address (delete: <CIU=0> ).
When communicating via HART , delete the part with the CIU address. Make transmission address 00:
®
<TA=00> to communicate with the gauge set on default address. Click on OK.