operation manual
59
Start-up
• Place the voltage supply unit (F) into the flush-
mounted box and fix it the flush-mounted box
using the supply screws.
• Place the frame of your installation and the sup-
plied clip-on frame (A) on the voltage supply unit.
• Place the electronic unit (B) of the wall thermo-
stat into the frame (see fig. 5).
• Switch the fuse of the power circuit on again (see
„5.1 Installation instructions“ on page 56) to
activate the teach-in mode of the device (see fol-
lowing section).
5.3 Behaviour after switching on the mains
voltage
If the device has not yet been connected, teach-in mode
will be activated during the first 3 minutes after the mains
voltage has been switched on. You will find further infor-
mation about connecting your device in the next section.
During the first 10 minutes after the mains voltage has
been switched on the device remains in start mode. Dur-
ing this time, the relay is being triggered.
During the following 20 minutes, the relay is operated via
two-point control. If the temperature falls below the set-
point temperature, the relay is switched on. If the setpoint
temperature is increased, the relay is switched o. After
20 minutes, the relay is operated via PI control with PWM
output (normal operation).