Hazard information
The actuator is part of the building installation.
The relevant national standards and directives
must be taken into consideration during planning
and set-up. The device has been designed solely
for operation on a 230V/50 Hz AC supply. Only
qualified electricians (to VDE 0100) are permitted
to carry out work on the 230 V mains. Applicable
accident prevention regulations must be
complied with whilst such work is being carried
out. To avoid electric shocks from the device,
please disconnect the
mains voltage (trip the
miniature circuit-breaker).
Non-compliance with
the installation instructions can cause fire or
introduce other hazards.
When connecting to the device terminals, take
the permissible cables and cable cross sections
into account.
The circuit to the which the device will be connect-
ed has to be secured by a cable protection switch in
accor
dance with EN60898-1 (tripping characteristic
B or C, max. 16 A rated current, min. 6 kA interrupt
-
ing rating, energy limiting class 3). Installation regu-
lations according to VDE 0100 and HD382 or 60364
ha
ve to be considered. Users must be able to easily
access the cable protection switch. This must be
marked as disconnecting device for the actuator.