Instructions

47
Start-up
Disconnect the power distribution panel from the
mains (see figure 2) and, if necessary, cover any
live parts (see safety rules).
Remove the cover from the power distribution
panel.
Place the blind actuator onto the DIN rail (see
figure 3). Make sure that you can read the letters
on the device and display and that the connecting
terminals of channel 1 and 2 are at the top.
Make sure that the catch spring (I) engages
properly and that the device is securely seated on
the rail (see figure 4).
Wire the device according to the connecting
diagrams in figure 6 or 7.
To enable power supply for the blind actuator,
connect the neutral conductor to terminal K and
the phase conductor to terminal J (see figure 7).
You can connect any types of phase conductors
(L1, L2, L3).
Connect the phase conductor for the selected
channel to the corresponding terminal (G) (see
figure 6). Any types of phase conductors (L1,
L2, L3) can be connected to the power input
terminals.
Connect the switched phase conductor to move
the blinds up for the selected channel to the
corresponding terminal (
) (F) (see figure 6+7).
Connect the switched phase conductor to move